Thermal performance analysis of closed wet cooling towers under both unsaturated and supersaturated conditions ( SCI-EXPANDED收录 EI收录)
文献类型:期刊文献
英文题名:Thermal performance analysis of closed wet cooling towers under both unsaturated and supersaturated conditions
作者:Zheng, Wei-Ye[1];Zhu, Dong-Sheng[1];Zhou, Guo-Yan[1];Wu, Jia-Fei[1];Shi, Yun-Yi[1]
机构:[1]E China Univ Sci & Technol, Sch Mech & Power Engn, Key Lab Pressure Syst & Safety MOE, Shanghai 200237, Peoples R China
年份:2012
卷号:55
期号:25-26
起止页码:7803
外文期刊名:INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
收录:;EI(收录号:20124215585533);WOS:【SCI-EXPANDED(收录号:WOS:000311196200042)】;
基金:The work was financially supported by Cultivation Fund for Interdisciplinary and Major Project (MOE) (2010JB0621) and Natural Science Foundation of China under Grant No. 50905060.
语种:英文
外文关键词:Poppe method; Closed wet cooling tower; Heat and mass transfer; Thermal performance
摘要:A closed wet cooling tower (CWCT) can be regarded as a cooling tower with the packing replaced by a bank of tubes. The heat and mass transfer in CWCT has been little investigated under supersaturated condition. The governing equations for heat and mass transfer in CWCT under both unsaturated and supersaturated conditions were derived based on Poppe method. Based on a sectional method, two analytical models were proposed and a program was coded to investigate the thermal performance by automatically selecting the corresponding governing equations whether the air was supersaturated or not. The results show that the air temperature, humidity ratio and enthalpy distributions under both unsaturated and supersaturated conditions could be accurately predicted with the analytical models. Then the effect of degree of saturation of inlet air on the heat transfer rate and process-water outlet temperature was presented, and little difference was found between the unsaturated and supersaturated conditions if the outlet air was supersaturated. (C) 2012 Elsevier Ltd. All rights reserved.