详细信息
On-line reset control of a commercial-scale opposed multi-burner coal-water slurry gasification system using dynamic reduced-order model ( SCI-EXPANDED收录 EI收录)
文献类型:期刊文献
英文题名:On-line reset control of a commercial-scale opposed multi-burner coal-water slurry gasification system using dynamic reduced-order model
作者:Qiu, Peng[1];Dai, Zhenghua[1];Xu, Jianliang[1];Guo, Qinghua[1];Yu, Guangsuo[1];Wang, Fuchen[1]
机构:[1]East China Univ Sci & Technol ECUST, Shanghai, Peoples R China
年份:2020
卷号:143
外文期刊名:COMPUTERS & CHEMICAL ENGINEERING
收录:;EI(收录号:20203609130924);WOS:【SCI-EXPANDED(收录号:WOS:000598171400015)】;
基金:This work is financially supported by the National Key R&D Plan (Grant No. 2018YFC0808500; 2017YFB0602600) and the National Natural Science Foundation of China (Grant No. 21776086; 21761132034).
语种:英文
外文关键词:On-line reset control; Opposed multi-burner; Gasification; Gasifier; Reduced-order model; Dynamic simulation
摘要:The entrained flows from four opposed burners enhance the mixing in a coal-water slurry (CWS) gasifier, which increases the extent of carbon conversion. Moreover, the operation of the opposed multi-burner (OMB) gasifier is more flexible because one couple of the opposed burners is allowed to be shut off for a certain period as long as the other couple is still running. Thus, the operation lifetime of the gasification system is determined by the ability to return the shut-off burners to operation, referred to as online reset control (ORC). However, the ORC is manual, which increases the operation uncertainty. In this study, we demonstrate an automatic control strategy using a dynamic reduced-order model (ROM). A reactor network model (RNM) of the gasifier, which considers several sub-models, is developed based on a flow field analysis and particle and gas residence time distributions (RTDs). The dynamic ROM and simulated manual ORC are verified using industrial data (5.8 MPa, 1500 metric tons per day (TPD)). An automatic control scheme for the ORC is proposed. The dynamic ROM is validated to be reliable when operating with the commercial-scale OMB CWS gasification system, as well as with its manual ORC process. The automatic ORC is promising for industrial gasification because the fluctuation ranges of the operation temperature and pressure of the gasifier are acceptable, which indicates that the reliable dynamic ROM can simulate a closed-loop control for a complex reactor. (C) 2020 Elsevier Ltd. All rights reserved.
参考文献:
正在载入数据...